MAIN MENU

CATALOG INDEX
BY ALPHABETICAL
ORDER

CATALOG INDEX
BY DEPARTMENT

For more info:
JSi@jsits.com

- [ Air Velocity
Temperature Relative
Humidity in One Meter
]
- [
VelociCalc Air Velocity
meters ]
- [
VelociCalc Plus
multi-parametter
ventilation meters ]

VelociCalc Plus ¸ÖƼ Æз¯¸ÞŸ º¥Æ¿·¹ÀÌ¼Ç ÃøÁ¤±â (ventilation meters )

velocicalc-plus_multiparameter-ventilation-meters.jpg (7206 octets)TSI's VelociCalc¢ç Plus Meters

 

 

 

 

 

»ç¾ç

Velocity from thermal sensor

Range

0 to 9,999 ft/min (0 to 50 m/s)

Accuracy

3.0% of reading or ¡¾3 ft/min (.015 m/ss) whichever is greater

Resolution

1 ft/min (0.01 m/s)

ÆÄÀÌ·ÎÆ® Æ©ºê¿¡¼­ÀÇ ¼Óµµ(Model 8583[A] & 8386[A])

Range

250 to 15,500 ft/min (1.27 to 78.8 m/s)

Accuracy

¡¾1.5% at 2,000 ft/min (10.16 m/s)

Resolution

1 ft/min (0.01 m/s)

ºÎÇÇÀÇ ¼Óµµ

Range

Actual range is a function of maximum velocity, pressure, duct size, and K factor

Duct size

Range

1 to 250 in. in increments of 0.1 in. (1 to 635 cm in increments of 0.1 cm)

Static/differential pressure (Model 8583[A] & 8386[A])

Range

-5 to +15 in H2O
(-9.3 to +28.0 mmHg, or -1245 to +3735 Pa)

Accuracy

¡¾1% of reading ¡¾0.005 in. H2O (¡¾1 Pa or ¡¾0.01 mmHg)

Resolution

0.001 in. H2O (1Pa, 0.01 mmHg)

ÃøÁ¤ ¿Âµµ ¹üÀ§

Operating (probe 8384[A] & 8385[A])

0 to 200¡ÆF (-17.8 to 93.3¡ÆC)

Operating (probe 8386[A])

14 to 140¡ÆF (-10 to 60¡ÆC)

Operating (electronics)

40 to 113¡ÆF (5 to 45¡ÆC)

Storage

-4 to 140¡ÆF (-20 to 60¡ÆC)

Resolution

0.1¡ÆF (0.1¡ÆC)

Accuracy

¡¾0.5¡ÆF (¡¾0.3¡ÆC)

ºñ±³½Àµµ(Model 8386[A] )

Range

0 to 95% rh

Accuracy

¡¾3% rh

Resolution

0.1% rh

Wet bulb ¿Âµµ(Model 8386[A])

Range

40 to 140¡ÆF (5 to 60¡ÆC)

Resolution

0.1¡ÆF (0.1¡ÆC)

À̽½Á¡(Model 8386[A] only)

Range

5 to 120¡ÆF (-15 to 49¡ÆC)

Resolution

0.1¡ÆF (0.1¡ÆC)

Heat flow (Model 8386[A] only)

Range

Function of flow rate, temperature, humidity and barometric pressure

Measurements available

Sensible Heat Flow, Latent Heat Flow, Total Heat Flow and Sensible Heat Factor

Units measured

BTU/h, kW

µ¥ÀÌÅÍ ÀúÀå ´É·Â

Range

Up to 1934 samples and 275 test id's (one sample can contain up to all eleven measurement types)

Interval

2 sec, 5 sec, 10 sec, 15 sec, 20 sec, 30 sec, 60 sec, 2 min, 5 min, 10 min, 15 min, 20 min, 30 min, 60 min

Time constant

Interval

1 sec, 2 sec, 5 sec, 10 sec, 15 sec, 20 sec

¿ÜÇü

Size measurements

4.2x7.2x1.5 inches (10.7x18.3x3.8 cm)

ÇÁ·Îºê ¿ÜÇüÄ¡¼ö

Probe length

40 in. (101.6 cm)

Probe diameter of tip

0.276 in. (7.01 mm)

Probe diameter of base

0.395 in. (10.03 mm)

ÇÁ·Îºê¸¸ÀÇ ¿ÜÇüÄ¡¼ö

Articulating section length

6.4 in. (16.26 cm)

Diameter of articulating Knuckle

0.372 in. (9.44 mm)

¹«°Ô

Weight (with batteries)

1.2 lbs (0.54 kg)

Àü¿ø

Requirement

Four AA-size batteries (included) or AC adapter (optional)

Model

8385

8386

Velocity

x

x

Volumetric Flowrate

x

x

Temperature

x

x

Differential pressure

x

Thermal/Pilot

x

Humidity

 

Dew point

 

Wet bulb temperature

 

Heat flow temperature

 

Data logging/Downloading

x

x

Statistics/Review data

x

x

Density correction factor

x

x

Variable time ontant

x

x

Printer output

x

x

NIST calibration certificate

x

x