MAIN
MENU
CATALOG INDEX BY ALPHABETICAL ORDER
CATALOG
INDEX BY DEPARTMENT
For more info: JSi@jsits.com
- [ Portable
Flue Gas / Combustion
Analyzer Model Eurolyzer ] - [ Portable
Flue Gas / Combustion
Analyzer Model ICA ] - [ Portable Flue Gas
/ Combustion
Analyzer Model
Megacom ]
|
Portable Flue Gas /
Combustion Analyzer Model: ICA
Features:
- Measures: Draft, O2,CO-H2 compensated, Flue
gas and ambient Temperatures
- Calculates: CO2, CO-undiluted, Efficiency, Excess air
(Lambda) and Losses
- Optionally measures NO & SO2 and calculates
NOx
- The sensors are safe for storage to -22F (-30C)
- Ideal for monitoring and servicing industrial combustion systems
- 2 separate pumps for gas and flush operations
- Datalogger can store 10 blocks of data
- Selective filter protection for sensors ensures maximum service life
- Integral printer and RS-232 serial interface
- Displays eight readings simultaneously
- Automatic self test and calibration
Specifications
- Flue Gas Temperature:
-
Sensor: |
K-type Thermocouple |
Range: |
32to 1,850F (0to 1,000C) |
Resolution: |
1F or C |
Accuracy: |
2F / 1C (0to 400C)
0.5% of reading (up to 1,000C) |
- Ambient Room Temperature:
-
Sensor: |
K-type Thermocouple |
Range: |
-5to 212F (-20° to 100C) |
Resolution: |
0.1F or C |
Accuracy: |
2F / 1C (0.1to 100C)
6F / 3C (-20to 0.0C) |
- Oxygen (O2) Measurement:
-
Sensor: |
Electro-chemical cell |
Range: |
0.0 to 20.9% |
Resolution: |
0.1% |
Accuracy: |
±0.2% |
- Carbon monoxide (CO) Measurement:
-
Sensor: |
Electro-chemical cell |
Range: |
0 to 2,000 ppm |
Resolution: |
1 ppm |
Accuracy: |
5 ppm (<150 ppm)
5% of reading (up to 2,000 ppm) |
- Draft Measurement:
-
Sensor: |
Semiconductor sensor |
Range: |
8.00 inches H2O or 19.99 mbar |
Resolution: |
0.01 inches H2O or mbar |
Accuracy: |
0.01 inches H2O / 0.02 mbar (<0.8 inches
H2O)
0.1% of reading (0.8 to 8.0 inches H2O) |
- Carbon dioxide (CO2) Calculation:
-
|
Calculated from O2 measurement |
Range: |
0.0 to CO2max %* |
Resolution: |
0.1% |
Accuracy: |
0.2% |
|
*CO2max % - Maximum CO2 value
(relative to fuel) in %
|
Display: |
Four line LCD - eight readings (backlit) |
Datalink: |
RS-232 serial port |
Integral Printer: |
Seico with plain 60 mm paper |
Operating Temperature: |
50to 104F (10to 40C) |
Storage Temperature: |
-22to 140F (-30to 60C) |
Power Supply: |
6V Ni Cad battery with charger |
Dimensions: |
9.5" X 4.0" X 8.25" |
- Items supplied with the ICA: pacer-indcom
-
|
Factory calibrated and installed oxygen, carbon monoxide and
draft sensors
Rechargeable battery and charger
Built in printer
1 pc. flue gas temperature probe / watertrap with 8' hose assembly
1 pc. ambient temperature sensor
1 pc. carrying case
1 pc. instruction manual
|
- Optional:
|
Soot pump PN 7112
Immersion Temperature probe PN TK102
Surface Temperature probe PN TK103
Air Temperature probe PN TK104
Pipe Clamp-on Temperature probe PN TK107 |
|
second separate gas pump PN 7133
Optional sensors: |
- Nitrogen monoxide (NO) Measurement: PN 7130
-
|
Sensor: |
Electro-chemical cell |
|
Range: |
0 to 2,000 ppm |
|
Resolution: |
1 ppm |
|
Accuracy: |
5 ppm (50 to 100 ppm)
5% of reading (up to 2000 ppm) |
- High Concentration Carbon monoxide (CO) Measurement: PN
7131
-
|
Sensor: |
Electro-chemical cell |
|
Range: |
0 to 10,000 ppm |
|
Resolution: |
100 ppm or 0.01% Vol |
- Sulfur dioxide (SO2) Measurement: PN 7132
-
|
Sensor: |
Electro-chemical cell |
|
Range: |
0 to 2,000 ppm |
|
Resolution: |
1 ppm |
|
Accuracy: |
5 ppm (<100 ppm)
5% of reading (up to 2000 ppm) |
- Draft Measurement (High Range):
-
|
Sensor: |
Piezoresistive semiconductor sensor
|
|
Range: |
40.00 inches H2O or 99.99 mbar
|
|
Resolution: |
0.01 inches H2O or mbar |
|
Accuracy: |
0.02 inches H2O / 0.05 mbar (up
to 8.0 inches H2O)
1% of reading (8.0 to 40.0 inches H2O) |
- Nitrogen dioxide (NO2) Calculation:
-
|
|
Calculated from NO measurement |
|
Range: |
0 to 2,000 ppm |
|
Resolution: |
1 ppm |
|
Accuracy: |
5 ppm (<100 ppm) |
|