Micromanometers DP-CALC
Models 8702 and 8705

dp_calc_micromanometers.jpg (8899 octets)TSI's DP-Calc¢â Micromanometers allow you to easily make the HVAC pressure measurements. The DP-CALC measures static, total, and velocity pressures as well as pressure drops across filters, coils, fans, and diffusers. The microprocessor-based DP-CALC uses the latest electronic pressure transducer technology, eliminating sensitivity due to the orientation of the meter. Each model of the DP-CALC combines a lightweight and durable design with an easy to read display.

Model 8702/8705 Features and benefits

Additional features of Model 8705

Specifications

Pressure

Range

-1245 to +3735 Pa (-9.3 to 28.0 mm Hg, -5 to +15 in. H2O)

Accuracy

¡¾1% of reading ¡¾1 Pa
(¡¾1% of reading ¡¾0.01 mm Hg)
(¡¾1% of reading ¡¾0.005 in. H2O)

Resolution

Model 8702

1 Pa (0.01 mm Hg, 0.001 in. H2O)

Model 8705

0.1 Pa (0.001 mm Hg, 0.0005 in. H2O)

Velocity

Range

250 ft/min - 15,500 ft/min (1.27m/s to 78.7m/s

Accuracy

¡¾1.5% at 2,000 ft/min (10.16m/s)

Instrument temperature range

Operating range

32 to 158¡ÆF (0 to 70¡ÆC)

Storage range

-40 to 185¡ÆF (-40 to 85¡ÆC)

Averaging capacity (model 8702 only)

Range

Up to 255 values each of pressure and velocity

Flow rate (model 8705 only)

Displayed range

Up to 9,999,000 CFM, m©ø/h, l/s

K factor range

0.01 to 2

Logging capability (model 8705 only)

Range

Up to 1000 values

Intervals

2 sec, 5 sec, 10 sec, 15 sec, 20 sec, 30 sec, 60 sec, 2 min, 5 min, 15 min, 20 min, 30 min, 60 min

Time constant

Values

1, 5, 10, 15, or 20 seconds

Power requirements

Batteries

Four AA-size Alkaline or NiCd rechargeable

Approx. battery life

24 hour (Alkaline), 7 hour (NiCd)

AC adapter (optional)

7 VDC niminal, 300mA

Physical

External dimensions

3.9 in. x 6.6 in. x 1.5 in.
(100mm x 168mm x 38mm)

Weight (with batteries)

0.76 lb. (0.35 kg)

Display:

4-digit LCD, 0.6 in. (15 mm) digit height

Printer interface

Type

serial

Baud rate

1200

Features

8702

8705

Differential pressure

  •  
  •  

Static pressure

  •  
  •  

Velocity

  •  
  •  

Volumetric flowrate

 

  •  

Calculate average

  •  
  •  

Determines min/max

 

  •  

Variable time constant

  •  
  •  

Density correction

 

  •  

K factor

 

  •  

Data logging

 

  •  

Data downloading software

 

  •  

Printer output

  •  
  •  

NIST calibration certificate

  •  
  •