- [ AirSense Model 310
Infrared CO2 Sensor
] - [ Carbon Dioxide
] - [ CO2 Ventostat
Wall Mount Monitor
] |
CO2 Ventostat Wall Mount Monitor
- Method: Dual Beam Absorption Infrared™ Patented
TEMA self calibration software
Optional thermistor temperature
measurement
- Sample Method: Diffusion or flow-through
(50-100
ml/min)
Accuracy
- Typical conditions 60-90°F(15-32°C): 0-2000 ppm:
+/-50 ppm or +/-3% of reading, whichever is greater 2,000-10,000 ppm:
+/-5% of reading
- Extended conditions 32-122°F (0-50°C): 0-2000 ppm:
+/-100 ppm or +/-5% of reading, whichever is greater 2,000-10,000 ppm:
+/-7% of reading
- Elevation (Pressure) Correction: Add 0.13% of
reading per mm Hg decrease from 760 (On-board correction, user set)
- Annual Drift: +/-10 ppm (negligible) with TEMA on
+/-20 ppm typical with TEMA off
- Response Time 0..90% FS: <2 min.
- Warm-Up Time @ 25 °C: <2 minutes
- Operating Conditions: 0°...50°C
(32°-122°F)
0°...95% RH, non-condensing
- Storage Conditions: -40°...70°C
- Agency Certification: FCC Part 15 Class B
- Calibration Interval: Five years/zero ppm gas
offset adjust
General Performance
- Measurement Range Analog output: 0-2000 ppm factory
default Adjustable to 10,000 ppm
- Digital display: 0-1-,000 ppm
- Sensitivity: +/-10 ppm
- Resolution: +/-1 ppm
Temperature Sensor
- Thermistor Standard: No Sensor
- Optional: User-specified, direct pass-through
connection (Consult factory)
Input/Output
- Power: 18-36 VAC RMS, 50/60 Hz 18-42 VDC polarity
protected/dependent
70 mA average, 100 mA peak, at 24 VDC
- Analog CO2 Output: 0-10 VDC (100 Ohms
output
impedence) 4-20 mA (RLmax = 500 Ohms) Both outputs
available simultaneously
- Relay: Normally Open or Normally Closed (wire
either way), gold bifurcated, 2A rating. Adjustable setpoint, factory
set at 1000 ppm, 50 ppm hysteresis.
- Wiring: 18-28 AWG stranded copper wire only. 2
wires each for power, analog output, relay, and optional thermistor.
- Ditital I/O: RS-232 interface, use with optional PC
software and cable in UIP kit 2072
CO2 Sensor Specification The CO2 sensor
for demand control ventilation shall be the 8002W non-dispersive infrared
sensor made by Engelhard Sensor Technologies (805-964-1699). The diffusion
gas chamber in the sensor should incorporate a reflective light pipe or
waveguide surrounded by a gas permeable 10 micron filter of 0.050"
thickness that prevents particulate contamination of the sensor. For long
term signal stability, the sensor shall utilize a dual channel infrared
detector, one channel for CO2 absorption, the other for reference. The
sensor shall incorporate elevation correction adjustment and Time Extended
Measurement Algorithm (TEMA) software for self correction of drift to
better than ±10 ppm per year. The sensor shall have accuracy of ±50 ppm
and repeatability of ±20 ppm. The sensor shall have a five year
recommended calibration interval. All adjustments to the sensor including
output scaling, elevation adjustment, relay setpoint, relay dead-band,
linear or exponential output, and single point calibration shall be made
via on-board push buttons and LCD display. The sensor shall also have
the capability for adjustment via computer connected to an on-board RJ45
jack. For ease of installation, the sensor shall have a detachable base
with all field wiring terminals on the base.
CAT. NO. |
DESCRIPTION |
TEL-8001W............. |
CO2 Wall Mount - no display, 0 - 10 VDC or
4-20 mA |
TEL-8002W............. |
CO2 Wall Mount - with display, 0 - 10 VDC or
4-20 mA |
TEL-8002P............... |
Pilot tube-Duct Mount |
TEL-1508................. |
Enclosure for Duct
Mount | |